10-5 3G3RV Register Numbers, Classes, Instances, and
Attributes

10-5-1 Inputting Control/Frequency (Read/Write)

The Inverter's various control inputs are allocated to the registers shown in the following table. For
example, to set the frequency reference and begin operation, first set the reference value to the fre-
quency reference register "0002," and then write the run command to the Inverter's run command
register "0001."
Note 1. Set values are retained until changed by the next writing operation.
Note 2. The following registers are in RAM, so they are all cleared to zero when the Inverter's power
supply is turned OFF.
Note 3. When the remote I/O function is being used, the run command and frequency reference are
overwritten at regular intervals.
Class 64
number (hex)
Instance Attribute
---
---
0000
00
01
0001
00
02
0002
---
---
0003 to 0005
00
06
0006
00
07
0007
00
08
0008
00
09
0009
10-42
Register
Reserved
Frequency reference
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10 to 15
Frequency reference (Set units using parameter o1-03.)
Not used.
PID target value
Analog output 1 setting ( − 11 V/ − 726 decimal to 11 V/726 decimal)
Analog output 2 setting ( − 11 V/ − 726 decimal to 11 V/726 decimal)
Multi-function contact output setting
Bit 0
Bit 1
Bit 2
Bit 3 to 5
Bit 6
Bit 7
Bit 8 to 15
Content
Run/stop command
Reverse/stop command 1: Reverse 0: Stop
Multi-function input command 3
Multi-function input command 4
Multi-function input command 5
Multi-function input command 6
Multi-function input command 7
Not used.
External error
Error reset
Not used.
Contact output (terminal M1-M2)
PHC1 (terminals P1-PC)
PHC2 (terminals P2-PC)
Not used.
Set error contact (terminal MA-MC) output using bit 7.
Error contact (terminal MA-MC)
Not used.
Chapter 10
1: Run 0: Stop
1: Error (EFO)
1: Reset command
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF