5-2-2 Switching with the Connection Path (Master)

Use the following procedure to switch the Master's remote I/O function with the Configurator. In this
example, the remote I/O function is set to Control I/O remote I/O + Unit status.
Procedure
1.Locate the Master in the Network Configuration Window and either double-click the Master or
right-click and select Parameters/Edit from the pop-up menu to display the Edit Device Parame-
ters Window. Select the desired Slave from the General Tab Page.
2.Click the
Note The Register/Unregister Button can be clicked at this point to allocate data with the remote
I/O function selected in the Slave. The following steps explain how to allocate data freely, so
steps 3 to 10 are not required if data will be allocated automatically. Proceed to step 11 (Down-
load) if using automatic allocation.
3.Select the desired Inverter from the General Tab Page and click the Advanced Setup Button.
5-6
Button to move the desired Inverter to the Register Devices List.
Chapter 5