Remote I/O Functions
Bit and Data Functions
Output Bit Details
Name
Forward/stop
Reverse/stop
Multi-function input @
External fault input
Fault reset
Multi-function contact
output
Multi-function output @ 0: Turn OFF (open) multi-function output @.
Note 1. The function set with the multi-function input selection parameters can be used by operating
multi-function input
3G3MV: The functions set in n052 to n056 (function selection for multi-function inputs 3 to 7) can be
used.
3G3RV/3G3PV:
The functions set in H1-01 to H1-05 (function selection for multi-function inputs 1 to 5) can
be used. (Multi-function input 6 is not used.)
3G3FV: The functions set in H1-01 to H1-06 (function selection for multi-function inputs 1 to 6) can
be used.
Note 2. The multi-function contact output and multi-function output
lowing parameters are set, so that the outputs in the Inverter's control terminals can be con-
trolled from communications.
3G3MV: Enabled when parameters n057 to n059 (function selection for multi-function outputs 1 to 3)
are set to 18 (12 hex) to specify communications output.
3G3RV/3G3PV/3G3FV:
Enabled when parameters H2-01 to H2-03 (function selection for the multi-function contact
output and multi-function outputs 1 and 2) are set to F (not used).
5-22
0: Stop, 1: Forward
0: Stop, 1: Reverse
0: ---, 1: Function set for multi-function input @
0: ---, 1: External fault (EFO) (See note 1.)
0: ---, 1: Reset
0: Turn OFF (open) multi-function contact output.
1: Turn ON (close) multi-function contact output.
(See note 2.)
1: Turn ON (close) multi-function output @.
(See note 2.)
.
@
Function
@
Chapter 5
will be enabled when the fol-