Message Communications
Instance
Attribute
01
09
Inverter Ready
0A
Fault
0B
Alarm (minor
fault)
0C
Fault Reset
0D
Fault code
0F
Control From
Net
Run signal input
status
(See note 2.)
10
DeviceNet Fault
mode
(See note 3.)
11
Force Fault/Trip
Communica-
tions external
fault input
12
Force Status
Communica-
tions external
fault input status
Note 1. The following table shows the status of remote I/O output signals and operation indicated by
the content of Attribute 06 (State, i.e., Inverter status).
Setting
00 hex
Vendor specific
01 hex
Startup: Preparation not complete (setting con-
stants)
02 hex
Not ready: Stopped (preparation complete)
03 hex
Inverter ready: Stopped (preparation complete) Inverter Ready signal is ON and Dur-
04 hex
Enabled: Operating
05 hex
Stopping: Decelerating (Operating with both
forward and reverse references equal to 0.)
06 hex
Fault_Stop: Operating with fault detected
07 hex
Faulted: Fault detected
Note 2. The Net Control and Control From Net functions cannot be changed during running.
Name
Content
00: Preparing
Initial processing/ not
drive mode/ fault
01: Inverter ready
Inverter can receive run
command.
00: Normal
01: Fault
00: Normal
01: Alarm (minor fault)
00: Normal status
01: Fault reset
Indicates the contents of
fault that occur. (See the
fault code list on the fol-
lowing page.)
00: Operating with an
n003/b1-02 setting other
than DeviceNet.
01: Operating by
DeviceNet.
00: Stop operation.
01: Continue operation.
02: Maker's specifications
00: Normal operation
01: Communications
external fault input
00: Normal status
01: Communications
external fault detected.
(Inverter stopped with fault
detection.)
Status
Setting range
Default
---
00
---
00
---
00
00, 01
00
---
0000
---
00
3G3MV: 00,
3G3MV:
01
00
3G3RV: ---
3G3RV:
3G3FV: ---
02
3G3FV:
02
00, 01
00
---
00
Condition
A condition other than the ones
below.
Inverter Ready signal is OFF.
Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
ing Run signal is OFF.
During Run signal (control I/O) is
ON.
Ctrl. From Net is ON, During For-
ward Run is OFF, During Reverse
Run is OFF, and During Run is ON.
Alarm signal is ON.
Fault signal is ON.
Chapter 6
Read
Write
Size
Yes
No
Byte
Yes
No
Byte
Yes
No
Byte
Yes
Yes
Byte
Yes
No
Word
Yes
No
Byte
Yes
Yes
Byte
Yes
Yes
Byte
Yes
No
Byte