Communications Errors
Note Check the Digital Operator display (see the following table) to identify faults when DeviceNet
communications are disabled.

Faults when DeviceNet Communications are Disabled

Inverter
3G3MV
3G3RV
3G3PV
3G3FV
F04
CPF04
---
ERR
F06
CPF06
F21
CPF21
F22
CPF22
F23
CPF23
Content
EEPROM fault
There was an inconsis-
tency in the stored data or
there is a hardware fault.
EEPROM write fault
Option Unit/Card self-test
error
Option Unit/Card self-test
error
Option Unit/Card model
code error
Option Unit/Card mutual
test error
A communications error
occurred between the
DeviceNet Communica-
tions Unit/Card and
Inverter.
Countermeasure
• Store the parameters again
• Turn the power supply OFF and then ON again.
• Replace the Inverter if the steps above do not elimi-
nate the fault.
Note: This fault may occur if the number of overwrite
operations exceeds 100,000. EEPROM is over-
written when a parameter change operation is
executed from a Parameter Unit or an ENTER
command is sent. Overwrite the data in EEPROM
as little as possible.
• Install the DeviceNet Communications Unit/Card cor-
rectly.
• Align the case with the connector of the DeviceNet
Communications Unit/Card so that it is fully installed.
• Install the DeviceNet Communications Unit/Card cor-
rectly.
• Turn the power supply OFF and then ON again.
• Replace the DeviceNet Communications Unit/Card if
the steps above do not eliminate the fault.
• Install the DeviceNet Communications Unit/Card cor-
rectly.
• Turn the power supply OFF and then ON again.
• Replace the DeviceNet Communications Unit/Card if
the steps above do not eliminate the fault.
• Install the DeviceNet Communications Unit/Card cor-
rectly.
• Align the case with the connector of the DeviceNet
Communications Unit/Card so that it is fully installed.
• Check whether the DeviceNet Communications Unit/
Card's FG wire is properly connected to the Inverter.
• Take steps to reduce noise in the DeviceNet commu-
nications lines. (See 3-3 Communications Line Noise
Prevention for details.)
• Replace the DeviceNet Communications Unit/Card if
the steps above do not eliminate the fault.