Omron 3G3MV-PDRT2 User Manual page 101

Devicenet communications units
Table of Contents

Advertisement

Remote I/O Functions
4.Click the Connection Tab of the Advanced Setting Window and select User Setup.
5.Select Use Poll Connection and Use COS connection.
6.Set Extended Control Status (Control I/O remote I/O) for the IN data and Extended Control Com-
mand (Control I/O remote I/O) for the OUT data as the poll connection's connection paths.
7.Set Unit Status for the IN data as the COS connection's connection path.
Note When a CS/CJ-series DeviceNet (Master) Unit is being used, set the COS connection's OUT
data to the same setting set for the poll connection's OUT data. If the connection paths do not
match, it will not be possible to select both Use Poll Connection and Use COS Connection.
Reference
The following connection path settings will be allocated automatically if you select the connection but
leave the connection path settings blank.
Connection
Poll
Slave's default connection path setting
Bit-strobe
Not allocated.
COS
Not allocated.
Cyclic
Not allocated.
8.Click the OK Button to close the Advanced Settings Window.
OUT (PLC → Inverter)
IN (PLC ← Inverter)
Slave's default connection path setting
Slave's default connection path setting
Unit Status 154 decimal (9A hex)
Unit Status 154 decimal (9A hex)
Chapter 5
5-7