Remote I/O Functions
Note 4. The P lock function (position lock or zero-servo function) is valid only for a 3G3FV Inverter
operating with flux vector control. This bit is not used with other Inverters or control modes.
Note 5. The output words (PLC to Inverter) allocated for the "control I/O remote I/O + Unit status"
function are the same as the output words allocated for the regular control I/O remote I/O
function. Just one word is added to the allocated input words (Inverter to PLC).
Reference
When a CS/CJ-series DeviceNet (Master) Unit is being used, we recommend allocating the Unit sta-
tus to a COS connection instead of using the default connection path setting. during normal opera-
tion, the status of the flags in the Unit status will not change, so allocation to a COS connection is
more efficient. If the Unit status is set in the default connection path, there input data occupies 5
words so the communications speed will be slower.