Inverter Outputs: Register Number 0009 Hex; Inverter Monitoring Functions; Class 64; Register Number (Hex) - Omron 3G3MV-PDRT2 User Manual

Devicenet communications units
Table of Contents

Advertisement

Appendices
Bit
7

Not used.

8
External fault input (1: EFO)
9
Fault reset (1: reset)
10 to 15
Not used.

Inverter Outputs: Register Number 0009 Hex

Bit
0
Multi-function contact output (1: ON)
1
Multi-function output 1 (1: ON)
2
Multi-function output 2 (1: ON)
3 to 15
Not used.
Note Valid when "18" (communications output) is set for multiple-function outputs 1 to 3 (n057 to
n059). By performing this setting, the relevant output terminal can be turned ON and OFF
through communications.

10-4-2 Inverter Monitoring Functions

All Inverter monitoring can be accessed. To read Inverter status, fault monitoring, alarm monitoring, I/
O status monitoring, error log, etc., specify the register number from the following table and read the
data.

Class 64

number (hex)
Instance Attribute
00
20
0020
00
21
0021
00
22
0022
00
23
0023
00
24
0024
00
---
0025 to 0027
00
28
0028
00
29
0029
00
2A
002A
00
2B

002B

00
2C
002C
00
2D
002D
00
2E
002E
00
---
002F to 0030
00
31
0031
00
32
0032
00
---
0033 to 0034
Content
Content
Register
Function
Status signal
Fault status
Data link status

Frequency reference

Output frequency

Not used.
Output voltage
Fault status 2
Warning status
Input terminal status
Inverter status
Output terminal status Refer to the following Output Terminal Status
Inverter status 2
Not used.
Main circuit DC voltage Read with 1 (V) = 1 decimal
Torque reference
Not used.
Content
Refer to the following Status Signals table.
Refer to the following Fault Status table.
Refer to the following Data Link Status table.
Follows setting for n035.
Follows setting for n035.
---
Read with 1 (V) = 1 decimal
Refer to the following Fault Status 2 table
Refer to the following Warning Status table
Refer to the following Input Terminal Status
table.
Refer to the following Inverter Status table.
table.
Refer to the following Inverter Status 2 table
---
Read with 1 (%) = 1 decimal
Rated motor torque = 100%.
Read with +/ − .
---
Chapter 10
10-31