10-4 3G3MV Register Numbers, Classes, Instances, and
Attributes

10-4-1 Inputting Control/Frequency

The Inverter's various control inputs are allocated to the registers shown in the following table. For
example, to set the frequency reference and begin operation, first set the reference value to the fre-
quency reference register "0002," and then write the run command to the Inverter's run command
register "0001."
Note 1. Set values are retained until changed by the next writing operation.
Note 2. The following registers are in RAM, so they are all cleared to zero when the Inverter's power
supply is turned OFF.
Note 3. When the remote I/O function is being used, the run command and frequency reference are
overwritten at regular intervals.
Class 64
number (hex)
Instance Attribute
---
---
0000
00
01
0001
00
02
0002
00
03
0003
---
---
0004 to 0008
00
09
0009
---
---
000A to 000F
Note 1. The V/f gain is the setting for the percentage of the V/f calculation result with respect to the
output voltage. A setting of 1000 decimal (03E8 hex) corresponds to a multiplication factor
of 1.
Note 2. When these registers are read, the values set in communications will be read. For example,
when an operation command (register number 0001) is read, the control input previously set
in communications will be returned. It is not a monitor for the actual terminal block input sig-
nals.

Run Commands: Register Number 0001 Hex

Bit
0
Forward/stop (1: forward operation)
1
Reverse/stop (1: reverse operation)
2
Multi-function input 3 (set with n052)
3
Multi-function input 4 (set with n053)
4
Multi-function input 5 (set with n054)
5
Multi-function input 6 (set with n055)
6
Multi-function input 7 (set with n056)
10-30
Register
Function
Not used.
Run command
Frequency reference
V/f gain
Not used.
Inverter output
Not used.
Content
Content
---
Refer to the following Run Commands table.
Frequency reference value setting (units as
specified in n035)
Make settings with 1000 decimal as 100%.
(See note 1.)
Setting range: 2.0 to 200.0% (20 to 2000
decimal)
---
Refer to following Inverter Outputs table.
---
Chapter 10