Configurator Settings
• The conduction time can be saved (written to the EEPROM) by clicking the Save Maintenance
Counter Button.
7-2-9 Network Power Supply Voltage Monitor
Functions
• The network power supply values are monitored with this function.
• The network power supply values (present value, maximum value, and minimum value) can be
recorded in the DeviceNet Communications Unit/Card.
• The network power supply voltage monitor value (factory setting: 11 V) can be set.
• When the voltage drops below the monitor voltage set in the Slave, the Network Power Voltage
Drop Flag turns ON in the Unit's Status Area.
Note 1. The communications power supply voltage for DeviceNet is a minimum of 11 V. Therefore,
if the power supply voltage is lower than 11 V, the Configurator or explicit messages may not
read process values correctly.
Note 2. The maximum and minimum values for the network power supply voltage are cleared when
the network power supply is turned OFF.
Setting Methods
1.Click the General Tab in the Edit Device Parameters Window.
2.Set the monitor voltage in the Network Power Voltage field.
7-36
General Tab Page in the
Edit Device Parameters
Window
Chapter 7