Step 3.
Remove the air baffle from the server and place it on a static-protective surface. See
air baffle" on page
Step 4.
Remove the M.2 backplane.
a.
Remove the screw that secures the end of the M.2 backplane to the air baffle.
b.
Remove the screw that secures the middle of the M.2 backplane to the air baffle
c.
Slide the M.2 backplane backward, and lift it out of the air baffle.
Figure 60. M.2 backplane removal
Step 5.
If needed, remove the M.2 backplane cables from the M.2 backplane.
a.
Unfasten the screw on the signal cable.
b.
Remove the M.2 backplane cables from the M.2 backplane.
Figure 61. M.2 backplane cable removal
After you finish
If you are instructed to return the component or optional device, follow all packaging instructions, and use
any packaging materials for shipping that are supplied to you.
65.
.
Chapter 5
Hardware replacement procedures