Parameter Assignment/Addressing
6.3 Options for Motor Menu (1) - first half
Table 6-3

Limits Menu (1120) Parameters

Parameter
ID
Overload select
1130
Overload pending
1139
Overload
1140
Overload timeout
1150
92
Unit
Default
Min
2 for in‐
verse time
with speed
derating
%
105.0 for
10.0
constant
and inverse
time set‐
tings
%
110.0 for
20.0
constant
and inverse
time set‐
tings.
100.0 for
Legacy TOL
modes.
sec
5.0 for in‐
0.01
verse time
modes.
60.0 for
constant
mode.
60.0 for
Legacy TOL
modes.
Max
Description
Select the overload trip algorithm:
Constant: fixed current-based TOL
Straight inverse time: motor tempera‐
ture-based TOL
Inverse time with speed derating: motor
temperature-based TOL
Legacy inverse time TOL (with or without
speed derating) for out-of-range motor
sizes.
Motor inertia must be accurate for the tem‐
perature model algorithm to work properly.
Note: Select "constant" and set the next two
parameters (1139 & 1140) to maximum to
disable this function.
210.0
Set the thermal overload level at which a
first level warning is issued:
Constant mode: based on motor total
current as a percent of rating.
Inverse mode: percentage of thermal ca‐
pacity based on the thermal model mo‐
tor heating.
This parameter is not used for legacy inverse
TOL options.
210.0
Set the motor thermal overload trip level and
an impending trip warning. Once this level is
reached, the timeout counter is started for
the overload fault.
Constant mode: based on motor total
current as a percent of rating.
Inverse mode: percentage of thermal ca‐
pacity based on the thermal model mo‐
tor heating.
Legacy inverse time TOL (with or without
speed derating) for out-of-range motor
sizes. Must be set to 100% for proper op‐
eration.
300.0
Set the time for the overload trip once the
overload trip level has been reached. Since
the inverse time algorithms estimate ther‐
mal heating of the motor, the overload time‐
out is minimal for trip.
NXGPro+ Control Manual
Operating Manual, A5E50491925A