Siemens SINAMICS PERFECT HARMONY GH180 Function Manual page 404

Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Software user interface
9.4 Security Measures
3. Insert FAT32-based USB flash disk into DCR.
4. Generate nxgupdate key via keypad parameter 7752.
– The file should be created within 30 seconds.
– You can remove the USB flash disk, insert into PC to check file creation. If trying to update
5. STOP HERE IF YOU ARE ONLY CREATING THE KEY
6. From ToolSuite Utilities tab, press NXGPro+ Initial Program button.
7. Select the NxGproPlus_vXXYYZZ_RNNN.init file, where XX, YY, ZZ is version and NNN is
release number. Wait for "Successfully loaded initialization file" success dialog and select OK.
Renaming "init" files IS NOT SUPPORTED; if renamed, the file will be ignored.
8. Reboot DCR (leave USB flash disk inserted).
9. Wait approximately 5-7 minutes for Green LED blink 7x repeatedly.
– If it does not (e.g. Red LED blink 15x repeatedly), recover FAILED
– If the DCR boots up normally and you can connect via Drive Tool or Debug Tool, then the
10.Remove USB flash disk from DCR.
11.Reboot DCR.
12.After ~60-90 seconds, you should be able to connect using Drive Tool and Debug Tool using
default IP configuration.
13.Now you will be able to reload customer-specific parameter configuration file and SOP file
from your PC.
14.Then reboot DCR again.
402
base software, then re-insert into DCR.
CAUTION
STOP HERE IF YOU ARE ONLY CREATING THE KEY
STOP HERE IF YOU ARE ONLY CREATING THE KEY; REMOVE USB FLASH DISK. PROCEEDING
WILL RESET YOUR DCR AND ERASE ALL SAVED PARAMETERS ON DCR.
USB flash drive was not recognized. Try another brand and/or model.