• currentplus.backup
• active SOP hex file
3B (Versions 8.1.0 amd above)
– Generate nxgemergency key files via keypad parameter 7751.
– Processing
– Please wait!
– Transferring
– Operation complete
If there are errors, then a generic error message will be displayed to see event log. The message
will be displayed for 10 seconds."
STOP HERE IF YOU ARE ONLY CREATING THE KEY FILES.
STOP HERE IF YOU ARE ONLY CREATING THE KEY FILES; REMOVE USB FLASH DISK and REBOOT
DCR. PROCEEDING WILL RESET YOUR DCR AND ERASE ALL SAVED PARAMETERS ON DCR.
Reboot DCR (leave USB flash disk inserted).
Wait approximately 5-7 minutes for Green LED blink 7x repeatedly.
• If it does not (e.g. Red LED blink 15x repeatedly), recover FAILED
• If the DCR boots up normally and you can connect via Drive Tool or Debug Tool, then the USB
flash drive was not recognized. Try another brand and/or model.
Remove USB flash disk from DCR and place into your PC.
Reboot DCR.
After ~60-90 seconds, you should be able to connect using Drive Tool and Debug Tool using
default IP configuration.
Now you will be able to reload customer-specific parameter configuration file and SOP file from
the USB flash disk.
Then reboot DCR again.
Parameter 7752 – to create update key and restore current DCR state
1. To save current parameter configuration and current SOP:
– from ToolSuite Drive Tool Host, Configuration → Save AS dto save current configuration
– from ToolSuite Drive Tool Host, Configuration → System Program → Upload System
2. On a PC, remove all secure USB key files from USB flash disk OR rename them.
NXGPro+ Control Manual
Operating Manual, A5E50491925A
Working...
CAUTION
parameter file to your PC
Program to save current SOP file to your PC.