Siemens SINAMICS PERFECT HARMONY GH180 Function Manual page 114

Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - first part
* Default values are highly recommended. Changing from defaults may have unintended re‐
sults.
Up and down transfer timeout "faults" create a drive alarm and return the drive to the prior
1
state before transfer was attempted. A reset must be issued to clear this "fault" before at‐
tempting another transfer.
Table 6-19
External I/O Menu (2800) Parameters
Parameter
ID
Analog inputs
2810
Analog outputs
2820
Digital inputs
2830
Digital outputs
2840
WAGO timeout
2850
Configuring the External I/O
The External I/O is configured from External I/O Menu (2800). You must define the total number
of I/O per the table for each type of I/O, analog I/O and digital I/O. If the I/O count is incorrect the
drive will indicate a "Wago configuration fault". Once the correct number of I/O is entered, clear
the fault by a fault reset.
For proper functioning of the WAGO timeout, the parameter Enable Watchdog (2971) must be
enabled. The Modbus coupler DIP switches must also be set correctly, these are configured at the
Siemens factory. Refer to Section User Inputs and Outputs in Chapter Hardware Interface
Description.
112
Unit
Default
Min
0
0
0
0
0
0
0
0
sec
10.0
0.0
Max
Description
24
Set the quantity of analog inputs in the at‐
tached external I/O.
16
Set the quantity of analog outputs in the at‐
tached external I/O.
96
Set the quantity of digital inputs in the at‐
tached external I/O.
64
Set the quantity of digital outputs in the at‐
tached external I/O.
600.0
Set the WAGO watchdog timeout period. Set
to 0 to disable this function.
NXGPro+ Control Manual
Operating Manual, A5E50491925A