Siemens SINAMICS PERFECT HARMONY GH180 Function Manual page 234

Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Operating the Control
7.15 Faults and Alarms
Fault handling
To reset a fault manually, use the [FAULT RESET] key on the keypad. Return the drive to the run
condition by performing manual start or by forcing the RunRequest_I equal to "true".
Certain faults can be reset automatically if enabled by the auto fault reset enable (7120). Refer
to Table Auto resettable faults, for a list of auto resettable faults. These are fixed and not
adjustable. If reset is successful, the drive will return to the run state automatically only if the
RunRequest_I is maintained at the value "true". The [FAULT RESET] key of the keypad is also
used to acknowledge alarms.
Table 7-4
Auto resettable faults
Over Speed Fault
Under Load Fault
Output Ground Fault
IOC
Menu Initialization
Medium voltage low Flt
Line Over Voltage Fault
232
Keypad Communication
Network 1 Communication
Network 2 Communication
Motor Over Volt Fault
Back EMF Timeout
Failed To Magnetize
Loss Of Field Current
Encoder Loss
Loss of Signal 1 to 24
Int AI1 to AI12 Loss of Signal
Loss Of Drive Enable
Motor Pull-out Fault
SMDC PLL Start-up Fault
SM Pole Slip
NXGPro+ Control Manual
Operating Manual, A5E50491925A