Parameter
ID
Ground Fault
7106
Limit
Ground Fault
7107
Time Const
Dedicated Input
7108
Protect
Input Breaker
7125
Open Time
Test IP Interrupt
7126
Time
Drive Has Input
7127
Breaker
Table 6-90
Single Phasing Menu (7010) Parameters
Parameter
ID
SPD prop gain
7020
SPD integral
7030
gain
SPD threshold
7040
Table 6-91
Drive Security Reset and Secure System Keys (for USB flash disk)
Parameter
Reset Credentials
Create Factory Key
Create Restore Key
Create Emergency Key
Create Update Key
Parameter 7748, Reset Credentials, resets the ToolSuite nxgproplus user login password to
"nxgproplus".
Spare controllers are usually shipped with the following password scheme, unless otherwise
specified:
NXGPro+ Control Manual
Operating Manual, A5E50491925A
Unit
Default
%
40.0
sec
0.2
Off
sec
0.4
Function
Yes
Unit
Default
0.0
0.001
%
50.0
ID
Description
7748
Reset DCR password for use with ToolSuite
7749
Create nxgrecover.factory secure key file on USB
7750
Create nxgrecover secure key file on USB
7751
Create nxgemergency secure key file on USB
7752
Create nxgupdate secure key file on USB
DCR serial # example: Y20010001aa!
6.16 Options for Drive Protect Menu (7) - part 2
Min
Max
Description
0.0
100.0
Set the level above which the drive issues
an input ground fault alarm.
0.001
2.0
Set the time constant of filter used for
averaging input neutral voltage when de‐
tecting a ground fault.
Input protection uses dedicated inputs
and outputs controlled by NXGpro code.
Options are:
0.02
0.5
Set the maximum expected opening time
for the input breaker. This value is used for
Tamper Resistant Input Protection.
Test the input breaker interruption time
response time. Input breaker will open
during test.
Indicates that drive has input breaker that
is under NXGpro software control. Op‐
tions are:
Min
Max
Description
0.0
10.0
Single phase detector PI regulator propor‐
tional gain term.
0.0
1.0
Single phase detector PI regulator integral
gain term.
0.0
100.0
Regulator output level below which an
alarm is generated.
Parameter Assignment/Addressing
Off
On
Yes
No
159