Parameter Assignment/Addressing
6.6 Options for Drive Menu (2) - second part
Table 6-32
Internal Analog Input 8 Menu (2711) Parameters
Parameter
ID
Type
2712
Hardware Zero
2713
Hardware Span
2714
RTD Alpha Value
2105
Table 6-33
Internal Analog Input 9 Menu (2715) Parameters
Parameter
ID
Type
2716
Hardware Zero
2717
Hardware Span
2718
RTD Alpha Value
2106
Table 6-34
Internal Analog Input 10 Menu (2721) Parameters
Parameter
ID
Type
2722
Hardware Zero
2723
Hardware Span
2724
118
Unit
Default
Min
1
0
-200
1
0.75
0.39
0.1
Unit
Default
Min
1
0
-200
1
0.75
0.39
0.1
Unit
Default
Min
1
0
-200
1
0.75
Max
Description
Set the operational mode for internal AI8:
•
0 to 20 mA
•
4 to 20 mA
•
0 to 10 V
•
RTD
200
Internal analog input 8 zero
1.25
Internal analog input 8 span
0.7
Set the internal I/O RTD's analog input alpha
value.
Max
Description
Set the operational mode for internal AI9:
•
0 to 20 mA
•
4 to 20 mA
•
0 to 10 V
•
RTD
200
Internal analog input 9 zero
1.25
Internal analog input 9 span
0.7
Set the internal I/O RTD's analog input alpha
value.
Max
Description
Set the operational mode for internal AI10:
•
0 to 20 mA
•
4 to 20 mA
200
Internal analog input 10 zero
1.25
Internal analog input 10 span
NXGPro+ Control Manual
Operating Manual, A5E50491925A