Parameter Assignment/Addressing
6.4 Options for Motor Menu (1) - second half
Parameter
ID
Motor current
1301
limit 8
Speed at cur‐
1302
rent lim 8
Motor current
1303
limit 9
Speed at cur‐
1304
rent lim 9
Further Description of Current Limit Profile Function
The speed/current limit profile function can be added by modifying the SOP, This feature consists
of nine set points composed of a speed and current limit value per each point that make up the
total curve. The drive follows the curve made up of the nine set points, as shown in the figure
below. The purpose of this function is to allow the user to set a maximum current limit point
associated with a specified maximum speed point. This limit is not absolute, other factors may
occur causing the control to reduce the limit, as described below.
120
100
80
60
40
20
0
0
Figure 6-2
Estimated VFD Current Limit
Current Limit Profile Operation
SOP flags are used to activate this function and to indicate to the user when the function is
active. SOP flag CurrentLimitProfileEnable_O must be set true to enable the function.
The Current Profile Menu (ID 1092) is used to set the parameters of the profile.
98
Unit
Default
Min
%
100
10
%
100
-200
%
100
10
%
100
-200
730
960
1250
Max
Description
300
Current limit 8 set point for speed/current profile.
200
Motor speed point 8 on the speed/current profile curve.
300
Current limit 9 set point for speed/current profile.
200
Motor speed point 9 on the speed/current profile curve.
1560
1745
1985
speed (rpm)
2275
2585
3000
NXGPro+ Control Manual
Operating Manual, A5E50491925A