• 0 to 10 V
• -10 V to +10 V (Note: This option is not allowed to be selected if the analog source is one of
the internal I/O inputs.)
Define the minimum and maximum values for scaling, and the loss of signal (LOS) threshold and
action.
Table 6-63
Analog Input #1 Menu (4100) Parameters
Parameter
ID
Source
4105
Type
4110
Min input
4120
Max input
4130
Loss point threshold
4140
Loss of signal action
4150
Loss of signal set‐
4160
point
NXGPro+ Control Manual
Operating Manual, A5E50491925A
Unit
Default
Min
Off
4–20 mA
%
0.0
-300.0 300.0
%
100.0
-300.0 300.0
%
15.0
0.0
Preset
%
20.0
-200.0 200.0
Parameter Assignment/Addressing
Max
Description
Set the input source for analog input 1:
Off
Ext 1 to 24
Int 1 to 12
See Table Pick list for Analog Input Sources.
Set the operational mode for analog input 1:
0 to 20 mA
4 to 20 mA
0 to 10 V
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Minimum analog input.
Maximum analog input.
100.0
Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Select loss of signal action:
Preset
Maintain
Stop
Loss of signal preset speed.
6.11 Options for Auto Menu (4)