Siemens SINAMICS PERFECT HARMONY GH180 Function Manual page 144

Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
Table 6-67
Analog Input #5 Menu (4341) Parameters
Parameter
ID
Source
4342
Type
4343
Min input
4344
Max input
4345
Loss point threshold
4346
Loss of signal action
4347
Loss of signal set‐
4348
point
Table 6-68
Auxiliary Input #1 Menu (4500) Parameters
Parameter
ID
Source
4510
Type
4520
Min input
4530
Max input
4540
142
Unit
Default
Min
Off
4–20 mA
%
0.0
-300.0 300.0
%
100.0
-300.0 300.0
%
15.0
0.0
Preset
%
20.0
-200.0 200.0
Unit
Default
Min
Off
4–20 mA
%
0.0
-300.0 300.0
%
100.0
-300.0 300.0
Max
Description
Set the input source for analog input 5:
Off
Ext 1 to 24
Int 1 to 12
See Table Pick list for Analog Input Sources.
Note: Analog input number is redundant since the
menu displays the input number.
Set the operational mode for analog input 5:
0 to 20 mA
4 to 20 mA
0 to 10 V
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Minimum analog input.
Maximum analog input.
100.0
Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Select loss of signal action:
Preset
Maintain
Stop
Loss of signal preset speed.
Max
Description
Auxiliary input 1 source:
Off
Ext 1 to 24
Int 1 to 12
See Table Pick list for Analog Input Sources.
Set the operational mode for auxiliary input 1:
0 to 20 mA
4 to 20 mA
0 to 10 V
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Minimum auxiliary input.
Maximum auxiliary input.
NXGPro+ Control Manual
Operating Manual, A5E50491925A