Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - first part
Parameter
ID
AFE cell DC P gain
2587
AP cell DC I gain
2588
AP cell Id P gain
2589
AP cell Id I gain
2591
AP cell Id D gain
2592
AP cell Iq P gain
2593
AP cell Iq I gain
2594
AP cell Iq D gain
2595
AP diff temp fault lvl 2596
AP Mplx Data Select 2597
AP sync ang offset
2579
Set Angles
2598
AP cell ang off 1
2571
AP cell ang off 2
2572
AP cell ang off 3
2573
AP cell ang off 4
2574
AP cell ang off 5
2575
AP cell ang off 6
2576
AP cell ang off 7
2577
AP cell ang off 8
2578
Regen OV I gain
2623
Regen OV P gain
2624
110
Unit
Default
Min
1.24
0.5
4.8435
1
0.2187
0.0078
46.875
5.859
x100
0.0166
0
0.2187
0.0078
46.875
5.859
x100
0.0166
0
deg
24.0
10.0
Air Temp
deg
0
-180
deg
-181
-181
deg
-181
-181
deg
-181
-181
deg
-181
-181
deg
-181
-181
deg
-181
-181
deg
-181
-181
deg
-181
-181
0.0010
0.0001
0.0000
0.0000
Max
Description
3.3
Set the AFE cell DC control proportional con‐
stant.
10
Set the AP cell DC control integral constant.
4
Set the AP cell real current regulator propor‐
tional constant.
3000
Set the AP cell real current regulator integral
constant.
0.0333
Set the AP cell real current regulator deriva‐
tive constant.
4
Set the AP cell reactive current regulator pro‐
portional constant.
3000
Set the AP cell reactive current regulator in‐
tegral constant.
0.0333
Set the AP cell reactive current regulator de‐
rivative constant.
30.0
Set the AP cell maximum temperature differ‐
ential before fault.
Select the source of the AP cell multiplexed
data.
180
Set the AP cell carrier synchronous angle off‐
set for all cells. Use to offset drive carriers
among two or more drives.
Set the AP cell angles as they relate to the
primary voltage.
180
Set the AP cell angle offset from the trans‐
former primary voltage for this rank.*
180
Set the AP cell angle offset from the trans‐
former primary voltage for this rank.*
180
Set the AP cell angle offset from the trans‐
former primary voltage for this rank.*
180
Set the AP cell angle offset from the trans‐
former primary voltage for this rank.*
180
Set the AP cell angle offset from the trans‐
former primary voltage for this rank.*
180
Set the AP cell angle offset from the trans‐
former primary voltage for this rank.*
180
Set the AP cell angle offset from the trans‐
former primary voltage for this rank.*
180
Set the AP cell angle offset from the trans‐
former primary voltage for this rank.*
1.0000
Set the regen overvoltage rollback regulator
integral gain.
10.0000
Set the regen overvoltage rollback regulator
proportional gain.
1
1
NXGPro+ Control Manual
Operating Manual, A5E50491925A