Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
Table 6-64
Analog Input #2 Menu (4170) Parameters
Parameter
ID
Source
4175
Type
4180
Min input
4190
Max input
4200
Loss point threshold
4210
Loss of signal action
4220
Loss of signal set‐
4230
point
Table 6-65
Analog Input #3 Menu (4232) Parameters
Parameter
ID
Source
4233
Type
4234
Min input
4235
Max input
4236
Loss point threshold
4237
140
Unit
Default
Min
Off
4–20 mA
%
0.0
-300.0 300.0
%
100.0
-300.0 300.0
%
15.0
0.0
Preset
%
20.0
-200.0 200.0
Unit
Default
Min
Off
4–20 mA
%
0.0
-300.0 300.0
%
100.0
-300.0 300.0
%
15.0
0.0
Max
Description
Set the input source for analog input 2:
•
Off
•
Ext 1 to 24
•
Int 1 to 12
See Table Pick list for Analog Input Sources.
Set the operational mode for analog input 2:
•
0 to 20 mA
•
4 to 20 mA
•
0 to 10 V
•
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Minimum analog input.
Maximum analog input.
100.0
Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Select loss of signal action:
•
Preset
•
Maintain
•
Stop
Loss of signal preset speed.
Max
Description
Set the input source for analog input 3:
•
Off
•
Ext 1 to 24
•
Int 1 to 12
See Table Pick list for Analog Input Sources.
Set the operational mode for analog input 3:
•
0 to 20 mA
•
4 to 20 mA
•
0 to 10 V
•
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Minimum analog input.
Maximum analog input.
100.0
Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
NXGPro+ Control Manual
Operating Manual, A5E50491925A