Modbus Communication
3.3 Parameter Assignment/Addressing
Network 1 Parameters
Table 3-11
Network 1: Configure Menu (9900)
Parameter
ID
Network 1 Type
9901
Table 3-12
Network 1: Configure Parameters Menu (9902)
Parameter
ID
Modbus Baud Rate
9060
Modbus Parity
9047
Modbus Stop Bits
9048
Modbus Address
9070
Velocity Units
9080
Demand Scalar
9912
Aux Demand Scalar
9913
Network Timeout
9934
46
Unit
Default
Min
None
Unit
Default
Min
19200
None
1
1
1
%
1
-125
1
-125
0
0
Max
Description
Designate the type of external network connected to
the drive:
● None
● Modbus
● DeviceNet
● Profibus
● Ethernet Modbus
● ControlNet
● Ethernet I/P
Max
Description
Set the Modbus network baud rate:
● 1200
● 2400
● 4800
● 9600
● 19200
Set the Modbus parity:
● none
● odd
● even
Set the Modbus stop bits:
● one
● two
247
Set the address of the node on the Modbus network.
Designate the units for velocity values from the drive:
● %
● RPM
● Hz
125
Set the scalar for input demand reference from the
network.
125
Set the auxiliary scalar for input demand reference
from the network.
65535
Set the timeout for network determined to be non-re‐
sponsive.
NXGpro Communication