Hardware User Interface Description
5.3 User Accessible Interfaces
Note
Tripped Pre-charge Circuit Breaker Occurrences
The pre-charge circuit breaker shall be tripped if any of the following occurs:
• Over-voltage (>115%) occurs during pre-charge
• Under-Voltage Trip (PCVMRStatus_O)
• Input Protection Fault
• LFR Trip
• PB4/E-Stop
• M2 Contactor Open Status Failure
• Trip_CB2 (TripPrechargeCB2_O) is asserted
The SOP input control flags below are available for particular cell types using the pre-charge
function by selecting Type 4 pre-charge. No dedicated inputs are used.
Table 5-3
Type 4 SOP Input Control Flags
Flag
StartCellPrecharge_O
PrechargeM2CloseAck_O
PrechargeM1CloseAck_O
TripPrechargeCB2_O (SOP)
PCVMRStatus_O
CB2Status_O
There are 16 digital outputs on the first user I/O board:
• DO-0 to DO-15
There is one digital output on the system interface board:
• SIB M1 DOUT
Table 5-4
Type 4 Dedicated and SOP Outputs
Dedicated Output*
Terminal
DO-14
J4-7, 8, 9
PrechargeM2Close_I
Assigned out‐
put
OpenPrechargeCB_I
Assigned out‐
put
M1 DOUT
SIB 51, 53, 55 M1Permit‐
* Dedicated Output: Refer to specific drive wiring diagram for dedicated output designations
78
Function
PrechargeRequest
M2CloseACK
M1CloseACK
TripPrechargeCB2
PCVMRStatus
CB2Status
SOP Feedback
Function
CIMVType4
CIMV
SOP determined
M2Close
SOP determined
BreakerTrip
M1Close
Closed_I
Permissive
(TIMV)
Description
Request to start pre-charge
Feedback of M2 contact
Feedback of M1 contact
Request trip of pre-charge CB
Precharge voltage (CB UV trip) status - '1' = voltage okay
Precharge CB status - '1' = CB is closed
Description
Command to close M1
Command to close M2
Command to open (trip) pre-charge supply
breaker
If this signal is de-energized, the drive's medi‐
um voltage will trip immediately.
If the signal is not energized, it will be an in‐
hibit.