Siemens SINAMICS PERFECT HARMONY GH180 Function Manual page 143

Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Parameter
ID
Loss of signal action
4238
Loss of signal set‐
4239
point
Table 6-66
Analog Input #4 Menu (4332) Parameters
Parameter
ID
Source
4333
Type
4334
Min input
4335
Max input
4336
Loss point threshold
4337
Loss of signal action
4338
Loss of signal set‐
4339
point
NXGPro+ Control Manual
Operating Manual, A5E50491925A
Unit
Default
Min
Preset
%
20.0
-200.0 200.0
Unit
Default
Min
Off
4–20 mA
%
0.0
-300.0 300.0
%
100.0
-300.0 300.0
%
15.0
0.0
Preset
%
20.0
-200.0 200.0
Parameter Assignment/Addressing
Max
Description
Select loss of signal action:
Preset
Maintain
Stop
Loss of signal preset speed.
Max
Description
Set the input source for analog input 4:
Off
Ext 1 to 24
Int 1 to 12
See Table Pick list for Analog Input Sources.
Set the operational mode for analog input 4:
0 to 20 mA
4 to 20 mA
0 to 10 V
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Minimum analog input.
Maximum analog input.
100.0
Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Select loss of signal action:
Preset
Maintain
Stop
Loss of signal preset speed.
6.11 Options for Auto Menu (4)
141

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents