Parameter
ID
Regen Shift Angle
2625
DC Bus Reference
2626
* -181 indicates that AP cells are not installed on this rank.
1
Default values are recommended.

Table 6-18

Synchronous Transfer Menu (2700) Parameters
Parameter
ID
Phase I gain*
2710
Phase P gain*
2720
Phase offset
2730
Frequency offset
2750
Up transfer time‐
2760
out
1
Up transfer
2762
threshold
Down transfer
2770
timeout
2
Down transfer
2772
threshold
Sync transfer type 2775
NXGPro+ Control Manual
Operating Manual, A5E50491925A
Unit
Default
Min
deg
0.00
-11.25
%
100
Unit
Default
Min
2.0
0.0
4.0
0.0
deg
2.00
-90.00
%
0.5
-10.0
sec
0.0
0.0
%
5.0
0.0
sec
0.0
0.0
%
5.0
0.0
with Reac‐
tor
Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - first part
Max
Description
11.25
Regen angle adjustment.
Sets the AFE cell DC Bus reference value.
Possible selections are 100%, 101%, 102%,
103%, 104%, 105%.
NOTE: This parameter applies ONLY for Cell
Voltage type 600 AP AFE (PWM regen).
Max
Description
15.0
Phase integrator gain
12.0
Phase proportional gain
90.00
Specify the phase angle setpoint used dur‐
ing up transfer. This is set positive and ex‐
pressed in degrees leading to prevent power
flow back into drive.
10.0
Frequency offset used during down transfer
to establish torque current by driving the
speed regulator into limit.
600.0
If the time taken for up transfer exceeds this
value then an up transfer timeout fault is
generated.
Ensure this setting is greater than the accel‐
eration time setting (2270, 2290, or 2310).
Set to 0 to disable the timeout fault.
15
current instability threshold when line con‐
tactor closes
600.0
If the time taken for down transfer exceeds
this value then a down transfer timeout fault
is generated. This is unaffected by the accel‐
eration rate. Set to 0 to disable the timeout
fault.
15
motor voltage droop when line contactor
opens
Selects sync transfer with or without a reac‐
tor
"with Reactor"
"No Reactor"
1
111