Parameter Assignment/Addressing
6.6 Options for Drive Menu (2) - second part
Internal Analog Input Menus
Table 6-25
Internal Analog Input 1 Menu (2815) Parameters
Parameter
ID
Type
2816
Hardware Zero
2817
Hardware Span
2818
Table 6-26
Internal Analog Input 2 Menu (2825) Parameters
Parameter
ID
Type
2826
Hardware Zero
2827
Hardware Span
2828
RTD Alpha Value
2101
Table 6-27
Internal Analog Input 3 Menu (2835) Parameters
Parameter
ID
Type
2836
Hardware Zero
2837
Hardware Span
2838
RTD Alpha Value
2102
116
Unit
Default
Min
1
0
-200
1
0.75
Unit
Default
Min
1
0
-200
1
0.75
0.39
0.1
Unit
Default
Min
1
0
-200
1
0.75
0.39
0.1
Max
Description
Set the operational mode for internal AI1:
•
0 to 20 mA
•
4 to 20 mA
200
Internal analog input 1 zero
1.25
Internal analog input 1 span
Max
Description
Set the operational mode for internal AI2:
•
0 to 20 mA
•
4 to 20 mA
•
0 to 10 V
•
RTD
200
Internal analog input 2 zero
1.25
Internal analog input 2 span
0.7
Set the internal I/O RTD's analog input alpha
value.
Max
Description
Set the operational mode for internal AI3:
•
0 to 20 mA
•
4 to 20 mA
•
0 to 10 V
•
RTD
200
Internal analog input 3 zero
1.25
Internal analog input 3 span
0.7
Set the internal I/O RTD's analog input alpha
value.