12.6 High-speed Counter Function
Setting method using the
Signal
Counter_Configuration parameters
Input Z signal
Setting the reset operation conditions by setting
up the input Z signal function
Comparison
Setting the "Comparison match rising edge reset"
match status
or "Comparison match falling edge reset"
bit
function to "Reset"
(Note 1)
If you set the control 0 signal or control 1 signal as the enable operation condition, the count enable
request bit will be disabled.
● To use the input Z signal and comparison match flag as reset signals, turn ON the reset enable
request bit through user programs.
Preset count operation
● Preset count operation is used by allocating the preset function to the control flag.
● Preset count operation rewrites the count value as the preset value according to the change
(rising, falling, positive logic, or negative logic) of the control flag.
● Preset count operation can also be used to start counter operation from the preset value.
● Preset count operation can be set using the methods shown in the following table.
Types of control flag (preset processing)
Setting method using the
Signal
Counter_Configuration parameters
Preset request
- (No need to set)
bit
Input Z signal
Setting the preset operation conditions by setting
up the input Z signal function
● To set a preset value, you must use a user program to set a temporary preset value and turn
ON the preset value change request bit.
12-36
Reset condition
Preset condition