12.6 High-speed Counter Function
(Note 1)
The control 0 signal and control 1 signal cannot be assigned to the capture function if they are
assigned to the enable operation.
Setting item
Comparison match leading
edge reset / Comparison match
trailing edge reset
Comparison function (Settable for each counter)
Setting item
Select comparison function
Select comparison input
Set number of comparison data
If you select "Band comparison" or "Target value match comparison" for "Select comparison
function", set parameters for each comparison data item.
Setting item
Comparison data 0 to
Comparison data 15 (for band
comparison)
Comparison data 0 to
Comparison data 15 (for target
value match comparison)
(Note 1)
Lower and upper limits can be set within the range between the lower and upper limits for the counter.
For linear counters, set each limit so that the lower limit is less than the upper limit. For ring counters,
lower and upper limits can be set in any range.
External output function (Settable for each counter)
Setting item
External output 0 signal setting
External output 0 signal ON
hold time
External output 1 signal setting
12-24
Settings
Selects a comparison match flag that resets the count
value at the rising edge or falling edge.
Not reset / Reset
Settings
Not use / Band comparison / Target value match
comparison
Count value
Sets the number of data items to be compared
Setting range: 1 to 16
Settings
Specifies the lower and upper limits for each
(Note 1)
comparison data
Setting range: -2,147,483,648 to 2,147,483,647
Specifies the state of the comparison match flag when
the current value falls within the specified band
ON / OFF
Specifies target values for each comparison data
Setting range: -2,147,483,648 to 2,147,483,647
Comparison match flags to be set or reset can be
selected for each status (incrementation or
decrementation) of comparison data that has reached
the target value.
● Addition set pattern: Set / No change
● Addition reset pattern: Reset / No change
● Subtraction set pattern: Set / No change
● Subtraction reset pattern: Reset / No change
Settings
Not output / Output
Setting range: 0 to 1,000 (ms)
Not output / Output
Default value
Not reset
Default value
Not use
Count value
16
Default value
0
OFF
0
No change
Default value
Not output
0 ms
Not output
WUME-GM1RTXOP-01