Alcatel-Lucent 1850 TSS-60 Installation And System Turn-Up Manual page 71

Transport service switch
Table of Contents

Advertisement

Cable and fiber installation
............................................................................................................................................................................................................................................................
5. One DS1/DS3 Hybrid Cable Assembly is required for A/B function unit Group to
support use of the LNW39 (16DS1/3DS3), LNW84 (16DS1/3DS3), LNW111 (3DS3),
LNW112 (16DS1), LNW140 (16DS1) and LNW391 (16DS1/3DS3) Hybrid. Each
DS1/DS3 Hybrid Cable Assembly consists of two separate cable assemblies, both
containing 28 pairs of 24 gauge cable a Coaxial 735A cable. One cable is for input and
the other cable is for output.
6. When cabling the Alcatel-Lucent 1850 TSS-60 for office alarm applications, one
Office Alarm Cable Assembly is required for the bottom Alcatel-Lucent 1850 TSS-60
shelf in a bay frame. One Office Alarm Mult Cable Assembly is required for each
additional Alcatel-Lucent 1850 TSS-60 shelf in the bay frame. For example, if four
Alcatel-Lucent 1850 TSS-60 shelves are located in a single 7-foot bay frame, one
Office Alarm Cable Assembly and three Office Alarm Mult Cable Assemblies are
required.
7. These cables are used for IAO LAN (OSI/TCP-IP)/Front LAN (OSI/TCP-IP)
connection (J16 and Front LAN port). LAN 10BASE-T cross over cable should be
used if the shelf is directly connected to a PC and LAN 10BASE-T straight through
cable should be used if shelf is connected to a hub.
............................................................................................................................................................................................................................................................
365-372-603R2.0
Issue 1 January 2009
Planning
3 - 5