Cable and fiber installation
............................................................................................................................................................................................................................................................
Miscellaneous (environmental) discrete telemetry cable
installation
Description
The miscellaneous (environmental) discrete telemetry access allows the maintenance
center to control and monitor equipment collocated with the Alcatel-Lucent 1850 TSS-60.
The environmental control feature enables the maintenance center to remotely initiate up
to four contact closures at the remote terminal (RT) for equipment operation such as
pumps, generators, etc.
The environmental alarm status indications allow up to 18 miscellaneous user-settable
alarm status indications (SI) at the remote terminal for transmission toward the central
office.
Miscellaneous (environmental) discrete telemetry cable assemblies and the length options
are listed in
Procedure
This procedure is performed for Alcatel-Lucent 1850 TSS-60 shelves requiring
miscellaneous (environmental) discrete telemetry.
........................................................................................................................................................................................................................
1
Connect the miscellaneous discrete telemetry cable to the J20 MISC connector on the
backplane of the Alcatel-Lucent 1850 TSS-60 shelf per
discrete cable connection" (p.
............................................................................................................................................................................................................................................................
365-372-603R2.0
Issue 1 January 2009
Table 3-21, "Miscellaneous discrete cable assemblies" (p.
3-62).
Miscellaneous (environmental) discrete telemetry cable
Figure 3-17, "Miscellaneous
installation
3-64).
3 - 6 1