The tutorial in this section gives instructions on how to set up for
a bi-directional SmartLoop test, set up the launch compensation
function, make connections, do a test, and save the results.
When you do a bi-directional SmartLoop test, one OTDR test at
one end of the link gives you bi-directional results for both fibers.
Also, the tester automatically averages the bi-directional results
and includes the averaged results in the test record.
Figure 15 shows the equipment necessary for this tutorial.
A
Main tester with OptiFiber Pro
module installed
Three launch cords for launch,
tail, and loopback connections
(match the fiber to be tested)
OTDR port protector patch cord
and adapter (30 cm, 12 in)
Figure 15. Equipment for the SmartLoop Tutorial
52
D
C
B
E
H
F
Two singlemode adapters
Dual-fiber link or segment
Fiber cleaning supplies
FI-1000 video probe with USB
connector
AC adapter with line cord
(optional)
G
GPU52.EPS