Bi-Directional Testing - Fluke OF-500-01 OptiFiber Technical Reference Handbook

Of-500 series optifiber
Hide thumbs Also See for OF-500-01 OptiFiber:
Table of Contents

Advertisement

OF-500 OptiFiber Certifying OTDR
Technical Reference Handbook

Bi-Directional Testing

To test cabling in both directions and save the bi-directional
results, proceed as follows:
1
On the Job tab, enter names for END 1 and END 2 to
identify the ends of the cabling. Name END 1 as the
end you will test first.
2
Set THIS END to END 1.
3-38
3
Test all the cabling and save the results from END 1.
4
On the Job tab, change THIS END to END 2; then test all
the cabling from the other end. When you save each
result, use the same fiber ID you used for the results
from the first end. The ID will be in the IDs IN CURRENT
FOLDER list.
You can do bi-directional averaging in LinkWare
software. See the LinkWare online help for details.