Fluke Versiv Series Technical Reference Handbook page 642

Hide thumbs Also See for Versiv Series:
Table of Contents

Advertisement

Versiv Series Cabling Certification Product Family
Technical Reference Handbook
DSX-8000 Level 2G Accuracy Performance Parameters
Parameter
Baseline Field Tester
Frequency
range and
resolution
Dynamic
Accuracy
NEXT
Dynamic
Accuracy IL
Dynamic
Accuracy
ACR-F
Source/load
return loss
1000 to 2000 MHz:
Random
1 to 1000 MHz: 95 dB
Noise Floor
1000 to 1310 MHz:
180.2 - 85.2log(f/100)
1310 to 2000 MHz:
606
per IEC Guidelines (continued)
1 to 31.25 MHz: 150 kHz
31.25 to 100 MHz: 250 kHz
100 to 250 MHz: 500 kHz
250 to 600 MHz: 1 MHz
600 to 1000 MHz: 2 MHz
± 1.0 dB (FEXT dynamic accuracy is tested to ± 0.75 dB)
1 to 1000 MHz:
21 – 9 log(f/100),
20 dB maximum
12 dB
85dB
Field Tester with
Level 2G
Permanent Link
Adapter
± 0.75 dB
± 0.75 dB
1 to 1000 MHz: 19 – 9 log(f/100),
20 dB maximum
1000 to 2000 MHz: 10 dB
1 to 1000 MHz: 90 dB
1000 to 1310 MHz:
175.2 - 85.2log(f/100)
1310 to 2000 MHz: 80 dB
Field Tester with
Level 2G Channel
Adapter