Appendix C: Reference Methods for

Introduction

The following discussion uses the 1, 2, and 3 jumper
terminology for the names of the three common test
methods. See Appendix B for a cross-reference of the
method names in various standards.
TIA-526-14B and 526-7 specify the One-Cord
Reference method for measuring loss on multimode
premises fiber and Method A.1 for singlemode
premises fiber, respectively. Both are 1 jumper
reference methods.
The number of fiber connections represented in loss test results
depends on how many test reference cords you use to set the
reference. This appendix describes the three common reference
methods: 1, 2, and 3 jumper.
Use the Reference Method setting on the tester's TEST SETUP
screen to select the method you will use. This setting does not
change the loss measurements, but it can change the
result for test limits that use a calculated loss limit. For all test
limits, the tester saves this setting to show the reference method
you used.
Fiber Cabling
Notes
/
PASS
FAIL