1 Alarms
Remedy:
Program Continuation:
380050
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
380051
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
1-646
Check that the corresponding SDB
• contains a diagnostic slot for every slave and
• contains only slave entries relevant to the application.
In general, it is possible to include a superset of slaves in the SDB that are partially rele-
vant for different end versions of the product. However, this overloads the NC memory
and runtime capacity and should therefore be avoided in general.
If this alarm occurs, it is necessary to reduce the SDB to a minimum.
If the code for the error cause is 03, check that equidistance is activated in the SDB (using
STEP7 HW config).
If the alarm continues to occur, please make a note of the error text and contact the con-
trol system manufacturer.
Switch control OFF - ON.
Profibus-DP: multiple assignment of inputs on address %1
%1 = Logical address
Multiple assignments of input data have been detected in the logical address space. Log-
ical address: Base address of the address area defined several times
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
The address partitioning should be checked as follows:
Check for multiple assignments in the following machine data:
• MD 13050[1] - MD 13050[n]: n = highest axis index on control system
• MD 12970, 12971: PLC address area for digital inputs
• MD 12978, 12979: PLC address area for analog inputs
If no inconsistencies can be found in the parameters, compare the machine data with the
configuration in SDB1000. In particular, check that the lengths configured for the individ-
ual slots do not result in area overlaps. When you find the cause of the error, change the
machine data and/or SDB1000.
Switch control OFF - ON.
Profibus-DP: multiple assignment of outputs on address %1
%1 = Logical address
Multiple assignments of input data have been detected in the logical address space. Log-
ical address: Base address of the address area defined several times
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
The address partitioning should be checked as follows:
Check for multiple assignments in the following machine data:
• MD 13050[1] - MD 13050[n]: n = highest axis index on control system
• MD 12974, 12975: PLC address area for digital outputs
• MD 12982, 12983: PLC address area for analog outputs
If no inconsistencies can be found in the parameters, compare the machine data with the
configuration in SDB1000. In particular, check that the lengths configured for the individ-
ual slots do not result in area overlaps. When you find the cause of the error, change the
machine data and/or SDB1000.
Switch control OFF - ON.
 Siemens AG, 2004. All rights reserved
SINUMERIK 840D/840Di/810D Diagnostics Guide (DA), 10.04 Edition