Function description
Figure 6-29
For converters FSA...FSG, you must interconnect the feedback signals "STO is active" with
two digital outputs.
Procedure
1. Set p0730 = 1838.3
2. Set p0731 = 1838.4
You have interconnected the feedback signal for safety function STO with the digital outputs of
the converter.
Parameters
Number
p0730
p0731
r1838
Further information is provided in the parameter list.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC

Feedback signal "STO is active" via digital outputs

Name
BI: CU signal source for terminal DO 0
BI: CU signal source for terminal DO 1
CO/BO: Gating unit status word 1
.03 1 signal: Shutdown path STO_B is inactive
.04 1 signal: Shutdown path STO_A is inactive
Parameters (Page 467)
Advanced commissioning
6.3 Drive control
Factory setting
52.3