Function description
Figure 6-29
For converters FSA...FSG, you must interconnect the feedback signals "STO is active" with
two digital outputs.
Procedure
1. Set p0730 = 1838.3
2. Set p0731 = 1838.4
You have interconnected the feedback signal for safety function STO with the digital outputs of
the converter.
❒
Parameters
Number
p0730
p0731
r1838
Further information is provided in the parameter list.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Feedback signal "STO is active" via digital outputs
Name
BI: CU signal source for terminal DO 0
BI: CU signal source for terminal DO 1
CO/BO: Gating unit status word 1
.03 1 signal: Shutdown path STO_B is inactive
.04 1 signal: Shutdown path STO_A is inactive
Parameters (Page 467)
Advanced commissioning
6.3 Drive control
Factory setting
52.3
52.7
---
299