r0331[0...n]
Actual motor magnetizing current/short-circuit current / Mot I_mag_rtd act
Access level: 3
Can be changed: -
Unit group: -
Min:
- [Arms]
Description:
Induction motor:
Displays the rated magnetizing current from p0320.
For p0320 = 0, the internally calculated magnetizing current is displayed.
Synchronous motor:
Displays the rated short-circuit current from p0320.
Dependency:
If p0320 was not entered, then the parameter is calculated from the rating plate parameters.
r0332[0...n]
Rated motor power factor / Mot cos phi rated
Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the rated power factor for induction motors.
For IEC motors, the following applies (p0100 = 0):
For p0308 = 0, the internally calculated power factor is displayed.
For p0308 > 0, this value is displayed.
For NEMA motors, the following applies (p0100 = 1, 2):
For p0309 = 0, the internally calculated power factor is displayed.
For p0309 > 0, this value is converted into the power factor and displayed.
Dependency:
If p0308 is not entered, the parameter is calculated from the rating plate parameters.
Note
The parameter is not used for synchronous motors (p0300 = 2xx).
r0333[0...n]

Rated motor torque / Mot M_rated

Access level: 3
Can be changed: -
Unit group: 7_4
Min:
- [Nm]
Description:
Displays the rated motor torque.
Dependency:
IEC drives (p0100 = 0): unit Nm
NEMA drives (p0100 = 1): unit lbf ft
Note
For induction motors, r0333 is calculated from p0307 and p0311.
For synchronous motors, r0333 is calculated from p0305, p0316, p0327 and p0328.
p0335[0...n]

Motor cooling type / Mot cool type

Access level: 2
Can be changed: C2(1), T
Unit group: -
Min:
0
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
- [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: p0100
Max:
- [Nm]
Calculated: -
Scaling: -
Unit selection: -
Max:
128
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 6722
Factory setting:
- [Arms]
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
-
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
- [Nm]
Data type: Integer16
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0
523