Motor Configuration / Motor Config; Number Of Command Data Sets (Cds) / Cds Count; Number Of Drive Data Sets (Dds) / Dds Count - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Note
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Control Unit.
p0133[0...n]

Motor configuration / Motor config

Access level: 2
Can be changed: C2(1, 3)
Unit group: -
Min:
-
Description:
Configuration of the motor when commissioning the motor.
Bit field:
Bit
00
01
Dependency:
For standard induction motors (p0301 > 10000), bit 0 is automatically pre-assigned the connection type of the selected
data set.
For p0100 > 0 (60 Hz rated motor frequency), it is not possible to select bit 1.
See also: p0304, p0305, p1082
Note
For bit 00:
When changing the bits, the rated motor voltage p0304 and the rated motor current p0305 are automatically converted
to the selected connection type (star/delta).
For bit 01:
87 Hz operation is only possible in the delta connection type. When selected, the maximum speed p1082 is
automatically pre-assigned for a maximum output frequency of 87 Hz.
p0170

Number of Command Data Sets (CDS) / CDS count

Access level: 2
Can be changed: C2(15)
Unit group: -
Min:
2
Description:
Sets the number of Command Data Sets (CDS).
Dependency:
See also: p0010, r3996
NOTICE
When the data sets are created, short-term communication interruptions may occur.
Note
It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0180

Number of Drive Data Sets (DDS) / DDS count

Access level: 3
Can be changed: C2(15)
Unit group: -
Min:
1
Description:
Sets the number of Drive Data Sets (DDS).
Dependency:
See also: p0010, r3996
NOTICE
When the data sets are created, short-term communication interruptions may occur.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Signal name
Motor connection type
Motor 87 Hz operation
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Delta
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
4
Calculated: -
Scaling: -
Unit selection: -
Max:
4
Parameters
7.2 Parameter list
Data type: Unsigned16
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0000 bin
0 signal
FP
Star
-
No
-
Data type: Unsigned8
Dynamic index: -
Function diagram: 8560
Factory setting:
2
Data type: Unsigned8
Dynamic index: -
Function diagram: 8565
Factory setting:
1
499