p8401[0...2]

RTC date / RTC date

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets and displays the date on the real-time clock in year, month, and day.
The date is stored in the internal clock block in the drive and continues to run even if the supply voltage for the Control
Unit is interrupted (for approx. 5 days).
Recommendation:
When the date is set as an index, the day should always be written last because, if a date is invalid, the day is always
corrected to the last valid day in that particular month of the year.
Index:
[0] = Day (1 ... 31)
[1] = Month (1 ... 12)
[2] = Year (YYYY)
Note
The time from p8400 and p8401 is used to display the fault and alarm times.
When displaying the fault time and alarm time, the switchover to daylight saving time is not taken into account.
The parameter is not reset when the factory setting is restored (p0010 = 30, p0970).
RTC: Real-time clock
p8402[0...8]

RTC daylight saving time setting / RTC DST

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Setting the daylight saving time.
The factory setting corresponds to the time change for central european summer time (CEST). You only have to set
p8402[0] = 1 to activate CEST.
Index:
[0] = Difference (0 ... 3 hours)
[1] = Start of month (1 ... 12)
[2] = Start of the week of the month (1 ... 4, 6)
[3] = Start of weekday (1 ... 7)
[4] = Start of hour (0 ... 23)
[5] = End of month (1 ... 12)
[6] = End of the week of the month (1 ... 4, 6)
[7] = End of weekday (1 ... 7)
[8] = End of hour (0 ... 23)
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
9999
Calculated: -
Scaling: -
Unit selection: -
Max:
23
Parameters
7.2 Parameter list
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
[0] 1
[1] 1
[2] 1970
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
[0] 0
[1] 3
[2] 6
[3] 7
[4] 2
[5] 10
[6] 6
[7] 7
[8] 3