Ci: Torque Limit Lower / M_Max Lower; Co: Torque Limit Upper/Motoring Scaling / M_Max Up/Mot Scal; Co: Torque Limit Lower Scaling / M_Max Lower Scal; Co: Torque Limit Upper Without Offset / M_Max Up W/O Offs - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
p1523[0...n]

CI: Torque limit lower / M_max lower

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for the lower torque limit.
Dependency:
See also: p1520, p1521, p1522
DANGER
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
p1524[0...n]

CO: Torque limit upper/motoring scaling / M_max up/mot scal

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-2000.0 [%]
Description:
Sets the scaling for the upper torque limit or the torque limit when motoring.
Dependency:
p1400.4 = 0: upper/lower
p1400.4 = 1: motoring / regenerating
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
p1525[0...n]

CO: Torque limit lower scaling / M_max lower scal

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-2000.0 [%]
Description:
Sets the scaling for the lower torque limit.
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
r1526

CO: Torque limit upper without offset / M_max up w/o offs

Access level: 3
Can be changed: -
Unit group: 7_1
Min:
- [Nm]
686
Calculated: -
Scaling: p2003
Unit selection: -
Max:
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
2000.0 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
2000.0 [%]
Calculated: -
Scaling: p2003
Unit selection: p0505
Max:
- [Nm]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: CDS, p0170
Function diagram: 6020, 6630
Factory setting:
1521[0]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 5620, 5630
Factory setting:
100.0 [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6630
Factory setting:
100.0 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6060, 6630,
6640
Factory setting:
- [Nm]
SINAMICS G120X converter