Co: Technology Controller, Kp Adaptation Output / Kp Adapt Outp; Technology Controller Tn Adaptation Upper Value / Tn Adapt Upper Val; Technology Controller Tn Adaptation Lower Value / Tn Adapt Lower Val - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Dependency:
See also: p2310, p2311, p2312, p2313, p2314, r2316
Note
Kp adaptation is activated with p2252.7 = 1.
r2316

CO: Technology controller, Kp adaptation output / Kp adapt outp

Access level: 2
Can be changed: -
Unit group: -
Min:
-
Description:
Display and connector output for the output signal of the adaption of proportional gain Kp for the technology controller.
Dependency:
See also: p2252, p2310, p2311, p2312, p2313, p2314, p2315
p2317
CI: Technology controller Tn adaptation input value signal source / Tn adapt inp s_s
Access level: 2
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for the input value of the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2252, p2318, p2319, p2320, p2321, r2322
Note
Tn adaptation is activated with p2252.8 = 1.
p2318

Technology controller Tn adaptation upper value / Tn adapt upper val

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the upper value for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2319, p2320, p2321, r2322
Note
Tn adaptation is activated with p2252.8 = 1.
p2319

Technology controller Tn adaptation lower value / Tn adapt lower val

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the lower value for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2318, p2320, p2321, r2322
Note
Tn adaptation is activated with p2252.8 = 1.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
60.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
60.000 [s]
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
-
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
0
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
3.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
10.000 [s]