Advertisement

p1909[0...n]

Motor data identification control word / MotID STW

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the configuration for the motor data identification.
Bit field:
Bit
00
02
03
05
06
07
11
12
14
15
16
17
18
19
20
21
22
23
24
26
Note
The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature inductance
Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
Bit 19 = 1:
All parameters are automatically saved after a successful motor data identification.
If a speed controller optimization run is then selected, the parameters are only saved after this measurement has been
completed.
Bit 22 ... 24: only for reluctance motors
Bit 22 = 1:
Only that measurement is carried out that is required for the flying restart of a reluctance motor. The bit is reset after
a successful measurement
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Signal name
Stator inductance estimate no measurement
Rotor time constant estimate no measurement
Leakage inductance estimate no measurement
Determine Tr and Lsig evaluation in the time range
Activate vibration damping
Deactivate vibration detection
Deactivate pulse measurement Lq Ld
Deactivate rotor resistance Rr measurement
Deactivate valve interlocking time measurement
Determine only stator resistance, valve voltage fault, dead
time
Short motor identification (lower quality)
Measurement without control parameter calculation
After motID direct transition into operation
After MotID automatically save results
Estimate cable resistance
Calibrating the output voltage measurement
Only identify circle
Deactivate circle identification
Circle identification with 0 and 90 degrees
Measure with long cable
Calculated: CALC_MOD_ALL Data type: Unsigned32
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
7.2 Parameter list
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0000 0000 0000 0000 0000
0000 0000 0000 bin
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
721