Ferrite Sleeves On The Connecting Cables - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Wiring
4.1 Line supply and motor
To meet the requirements of conducted emissions in accordance with C1, you must observe
the maximum motor cable length and also install ferrite sleeves on the FSD ... FSF converter.
Converter frame
size
400 V
FSD
FSE
FSF
Install the ferrite sleeves as closely as possible to the converter terminals on the connecting
cables.
Figure 4-4
84
Ferrite sleeve
Schaffner RU41572-1
Schaffner VAC
W517-02
Schaffner RU41572-2

Ferrite sleeves on the connecting cables

Installation
1 ferrite sleeve per line terminal L1, L2 and L3
1 ferrite sleeve per motor terminal U2, V2 and W2
2 ferrite sleeves per line terminal L1, L2 and L3 and
2 ferrite sleeves per motor terminal U2, V2 and W2
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
SINAMICS G120X converter