Parameters
7.2 Parameter list
p0860

BI: Line contactor feedback signal / Line contact feedb

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for the feedback signal from the line contactor.
Recommendation:
When the monitoring is activated (BI: p0860 not equal to r0863.1), then to control the line contactor, signal BO: r0863.1
of its own drive object should be used.
Dependency:
See also: p0861, r0863
See also: F07300
NOTICE
The line contactor monitoring is deactivated if the control signal of the particular drive object is set as the signal source
for the feedback signal of the line contactor (BI: p0860 = r0863.1).
Note
The state of the line contactor is monitored depending on signal BO: r0863.1.
When the monitoring is activated (BI: p0860 not equal to r0863.1), fault F07300 is then also output if the contactor is
closed before it is controlled using r0863.1.
p0861

Line contactor monitoring time / LineContact t_mon

Access level: 3
Can be changed: T
Unit group: -
Min:
0 [ms]
Description:
Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the line
contactor within the time, a message is output.
Dependency:
See also: p0860, r0863
See also: F07300
Note
The monitoring function is disabled for the factory setting of p0860.
r0863.0...1

CO/BO: Drive coupling status word/control word / CoupleZSW/STW

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the status word and control word of the drive coupling.
Bit field:
Bit
00
01
Note
For bit 01:
Bit 1 is used to control an external line contactor.
594
Signal name
Closed-loop control operation
Energize contactor
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
5000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned32 / Binary
Dynamic index: -
Function diagram: 2634
Factory setting:
863.1
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 2634
Factory setting:
100 [ms]
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
No
-
No
2634
SINAMICS G120X converter