Co: Speed Limit In Positive Direction Of Rotation / N_Limit Pos - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Note
The parameter applies for both motor directions.
The parameter has a limiting effect and is the reference quantity for all ramp-up and ramp-down times (e.g. down
ramps, ramp-function generator, motor potentiometer).
The parameter is part of the quick commissioning (p0010 = 1); this means that it is appropriately pre-assigned when
changing p0310, p0311, p0322.
The following limits are always effective for p1082:
p1082 <= 60 x minimum (15 x p0310, 550 Hz) / r0313
p1082 <= 60 x maximum power unit pulse frequency / (k x r0313), with k = 12 (vector control), k = 6.5 (U/f control)
During automatic calculation (p0340 = 1, p3900 > 0), the parameter value is assigned the maximum motor speed
(p0322). For p0322 = 0 the rated motor speed (p0311) is used as default (pre-assignment) value. For induction motors,
the synchronous no-load speed is used as the default value (p0310 x 60 / r0313).
For synchronous motors, the following additionally applies:
During automatic calculation (p0340, p3900), p1082 is limited to speeds where the EMF does not exceed the DC link
voltage.
p1082 is also available in the quick commissioning (p0010 = 1); this means that when exiting via p3900 > 0, the value
is not changed.
p1082[0...n]
Maximum speed / n_max
G120X_DP (PM330),
Access level: 1
G120X_PN (PM330),
Can be changed: C2(1), T
G120X_USS (PM330)
Unit group: 3_1
Min:
0.000 [rpm]
Description:
Sets the highest possible speed setpoint.
Dependency:
The maximum speed is limited to: p1082 <= 60 x 150 Hz / r0313
See also: p0230, p0310, r0313, p0322
NOTICE
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note
The parameter applies for both motor directions.
The parameter has a limiting effect and is the reference quantity for all ramp-up and ramp-down times (e.g. down
ramps, ramp-function generator, motor potentiometer).
The parameter is part of the quick commissioning (p0010 = 1); this means that it is appropriately pre-assigned when
changing p0310, p0311 and p0322 (p0310 x 60 / r0313, for p0322 = 0).
p1083[0...n]

CO: Speed limit in positive direction of rotation / n_limit pos

Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.000 [rpm]
Description:
Sets the maximum speed for the positive direction.
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
626
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: p0505
Max:
210000.000 [rpm]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
210000.000 [rpm]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Dynamic index: DDS, p0180
Function diagram: 3020, 3050,
3070
Factory setting:
1500.000 [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3050
Factory setting:
210000.000 [rpm]
SINAMICS G120X converter