List Of Modified Parameters 10 / List Chang Par 10; Speed Setpoint Selection / N_Set Sel - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Note
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here. In a long
list, index 99 contains the parameter number at which position the list continues.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be read
from a higher-level control system (e.g. PROFIBUS master).
r0999[0...99]

List of modified parameters 10 / List chang par 10

Access level: 4
Can be changed: -
Unit group: -
Min:
-
Description:
Displays those parameters with a value other than the factory setting for this drive.
Dependency:
See also: r0990, r0991
Note
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be read
from a higher-level control system (e.g. PROFIBUS master).
p1000[0...n]

Speed setpoint selection / n_set sel

G120X_DP,
Access level: 1
G120X_PN
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the source for the speed setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
1:
2:
3:
6:
7:
10:
11:
12:
13:
16:
17:
606
No main setpoint
Motorized potentiometer
Analog setpoint
Fixed speed setpoint
Fieldbus
Analog setpoint 2
Motor potentiometer + no main setpoint
Motor potentiometer + motor potentiometer
Motor potentiometer + analog setpoint
Motor potentiometer + fixed speed setpoint
Motor potentiometer + fieldbus
Motor potentiometer + analog setpoint 2
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
200
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
-
Data type: Integer16
Dynamic index: CDS, p0170
Function diagram: -
Factory setting:
6