Function Description; Prerequisites For Sil 2/Pl D; Prerequisites For Sil 3/Pl E; Sirius 3Sk1 Safety Relay - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Prerequisites for SIL 2/PL d

● Suitable higher-level controllers
– SIRIUS 3SK1: Single-channel static feedback circuit
– SIRIUS 3SK2: Two-channel dynamic feedback circuit
– MSS 3RK3: Two-channel dynamic feedback circuit
– SIMATIC: Feedback circuit monitoring in the safety program
● Forced checking procedure (test stop) once per year

Prerequisites for SIL 3/PL e

● Suitable higher-level controllers
– SIRIUS 3SK1: Single-channel static feedback circuit
– SIRIUS 3SK2: Two-channel dynamic feedback circuit
– MSS 3RK3: Two-channel dynamic feedback circuit
– SIMATIC: Feedback circuit monitoring in the safety program
● Forced checking procedure (test stop) every 3 months

Function description

SIRIUS 3SK1 safety relay

Figure 4-27
You can achieve SIL 2/PL d with a SIRIUS 3SK1 safety relay and the converter FSA ... FSG.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Permissible for converters FSH and FSJ, not permissible for FSA ... FSG
Connection 3SK1 inside a control cabinet for FSA ... FSG
Wiring
4.2 Control interfaces
133

Advertisement

Table of Contents
loading

Table of Contents