Co/Bo: Hibernation Mode Status Words / Hib Zsw; Co: Fixed Value 1 [%] / Fixed Value 1 [%] - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Note
When the "hibernation mode" function (p2398 = 1) is activated, its behavior is defined as to whether the technology
controller is additionally switched in (closed-loop) or switched out (open-loop).
The technology controller is enabled via binector input p2200 and its mode is set in p2251.
p2200 = 0, p2251 = 0:
Hibernation mode operates without technology controller (open-loop)
p2200 = 1, p2251 = 0:
Hibernation mode operates with technology controller (closed-loop)
r2399.0...8

CO/BO: Hibernation mode status words / Hib ZSW

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the status word of the "hibernation mode" function.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
Dependency:
See also: p2398
See also: A07325
p2900[0...n]

CO: Fixed value 1 [%] / Fixed value 1 [%]

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-10000.00 [%]
Description:
Setting and connector output for a fixed percentage value.
Dependency:
See also: p2901, r2902, p2930
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
The value can be used to interconnect a scaling function (e.g. scaling the main setpoint).
824
Signal name
Hibernation mode enabled (p2398 <> 0)
Hibernation mode active
Hibernation mode delay active
Hibernation boost active
Hibernation mode motor switched off
Hibernation mode switched off cyclic restart active
Hibernation motor motor restarts
Hibernation mode supplies total setpoint for ramp-fct
generator
Hibernation mode bypasses ramp-fct generator in setpoint
channel
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
10000.00 [%]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Unsigned32
Dynamic index: -
Function diagram: 7038
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 1021
Factory setting:
0.00 [%]
SINAMICS G120X converter